Chapter 6 Fault Code Information and Maintenance|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

6-3

Fault

Name

Fault Descriptions

Corrective Actions

Over-current during
acceleration

1. Short-circuit at motor output: Check for

possible poor insulation at the output lines.

2. Torque boost too high: Decrease the torque

compensation setting in Pr.07.02.

3. Acceleration Time too short: Increase the

Acceleration Time.

4. AC motor drive output power is too small:

Replace the AC motor drive with the next
higher power model.

Over-current during
deceleration

1. Short-circuit at motor output: Check for

possible poor insulation at the output line.

2. Deceleration Time too short: Increase the

Deceleration Time.

3. AC motor drive output power is too small:

Replace the AC motor drive with the next
higher power model.

Over-current during
constant speed operation

1. Short-circuit at motor output: Check for

possible poor insulation at the output line.

2. Sudden increase in motor loading: Check for

possible motor stall.

3. AC motor drive output power is too small:

Replace the AC motor drive with the next
higher power model.

External Fault

1. When

multi-function

input terminals (MI3-MI9)

are set to external fault, the AC motor drive
stops output U, V and W.

2. Give RESET command after fault has been

cleared.

Internal EEPROM can not be
programmed.

Return to the factory.

Internal EEPROM can not be
programmed.

Return to the factory.

Internal EEPROM can not be
read.

1. Press RESET key to set all parameters to

factory setting.

2. Return to the factory.

Internal EEPROM can not be
read.

1. Press RESET key to set all parameters to

factory setting.

2. Return to the factory.

U-phase error

V-phase error

W-phase error

OV or LV

Temperature sensor error

Return to the factory.