beautypg.com

Delta Electronics AC Motor Drive VFD-E User Manual

Page 86

background image

Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-33

Overheat Warning

Applications Purpose

Functions

Related

Parameters

Air conditioner

Safety measure

When AC motor drive overheats, it
uses a thermal sensor to have
overheat warning.

03.00~03.01
04.05~04.08

Two-wire/three-wire

Applications Purpose

Functions

Related

Parameters

General application

To run, stop,
forward and
reverse by external
terminals

VFD-E

MI1:("OPEN":STOP)

("CLOSE":FWD)

MI2:("OPEN": STOP)

("CLOSE": REV)

DCM

FWD/STOP

REV/STOP

VFD-E

MI1:("OPEN":STOP)

("CLOSE":RUN)

MI2:("OPEN": FWD)

("CLOSE": REV)

DCM

RUN/STOP

FWD/REV

3-wire

VFD-E

MI3:("OPEN":STOP)

MI1 ("CLOSE":RUN)

:

MI2:("OPEN": FWD)

("CLOSE": REV)

DCM

STOP

REV/FWD

RUN

02.00
02.01
02.09
04.04

Operation Command

Applications Purpose

Functions

Related

Parameters

General application

Selecting the
source of control
signal

Selection of AC motor drive control by
external terminals, digital keypad or
RS485.

02.01

04.05~04.08

Frequency Hold

Applications Purpose

Functions

Related

Parameters

General application

Acceleration/
deceleration pause

Hold output frequency during
Acceleration/deceleration

04.05~04.08