3.3. proposal for the Installation and Setting of an Emergency Microphone
3.3.1. Installation place
the emergency microphone (rm-200SA in emergency mode, rm-200Sf) must be installed in access level 2.
to do so, either install the emergency microphone in a lockable (wall-mount) box or in a room with access only
by mechanical keys, access cards or entering a code of at least 3 manual sequential operations. the room or
the box must be accessible only for persons having a specific responsibility for safety and who are trained and
authorized to operate the emergency microphone in the voice alarm condition.
3.3.2. Settings
Depending on the requirements for the use of the emergency microphone, one or more VA zones or VA zone
groups shall be set. A possibility of starting the emergency shall be provided (by emergency pattern). fault
indications (fault receipt buttons) can be set when the emergency microphone is used for paging only. faults
receipt buttons for VA zones or VA zone groups must be set if a manual control of the emergency is provided.
When these fault receipt buttons are set, then these shall cover the same VA zones or VA zone groups as used
for the zone selection buttons. A general fault indication might be provided also.
3.3.3. Example for a setting on an emergency microphone
1 rm-200Sf and 1 rm-210
Figure 3: emergency microphone RM-200SF + RM-210 with manual VA control
(1) emergency reset
(2) general fault (fault receipt function)
(3) lamp test
(4) All-call (including all VA zones)
(5) VA zone 1 selection
(6) VA zone 1 speaker line fault receipt *
(7) VA zone 2 selection
(8) VA zone 2 speaker line fault receipt *
(9) VA zone 3 selection
(10) VA zone 3 speaker line fault receipt *
(11) VA zone 4 selection
(12) VA zone 4 speaker line fault receipt *
(13) VA zone 5 selection
(14) VA zone 5 speaker line fault receipt *
* not mandatory, can be replaced by VA zones
further VA zones or VA zone groups can be programmed on further rm-210.