3.3. proposal for the Installation and Setting of an Emergency Microphone

3.3.1. Installation place

the emergency microphone (rm-200SA in emergency mode, rm-200Sf) must be installed in access level 2.

to do so, either install the emergency microphone in a lockable (wall-mount) box or in a room with access only

by mechanical keys, access cards or entering a code of at least 3 manual sequential operations. the room or

the box must be accessible only for persons having a specific responsibility for safety and who are trained and

authorized to operate the emergency microphone in the voice alarm condition.

3.3.2. Settings

Depending on the requirements for the use of the emergency microphone, one or more VA zones or VA zone

groups shall be set. A possibility of starting the emergency shall be provided (by emergency pattern). fault

indications (fault receipt buttons) can be set when the emergency microphone is used for paging only. faults

receipt buttons for VA zones or VA zone groups must be set if a manual control of the emergency is provided.

When these fault receipt buttons are set, then these shall cover the same VA zones or VA zone groups as used

for the zone selection buttons. A general fault indication might be provided also.

3.3.3. Example for a setting on an emergency microphone

1 rm-200Sf and 1 rm-210

Figure 3: emergency microphone RM-200SF + RM-210 with manual VA control

(1) emergency reset

(2) general fault (fault receipt function)

(3) lamp test

(4) All-call (including all VA zones)

(5) VA zone 1 selection

(6) VA zone 1 speaker line fault receipt *

(7) VA zone 2 selection

(8) VA zone 2 speaker line fault receipt *

(9) VA zone 3 selection

(10) VA zone 3 speaker line fault receipt *

(11) VA zone 4 selection

(12) VA zone 4 speaker line fault receipt *

(13) VA zone 5 selection

(14) VA zone 5 speaker line fault receipt *
* not mandatory, can be replaced by VA zones
further VA zones or VA zone groups can be programmed on further rm-210.