Options requiring controls in access level 2 – Toa SX-2000 Series Installation User Manual

Page 190

background image

190

3.2. Options requiring Controls in Access Level 2

All the listed functions in the next table belong to the option with requirements "VA manual control" (§10).

No.

11

12

Indication/control

manual reset of

the VA condition

Indication of the

status of VA zones

/ zone groups

requirement and Preparation

requirement: this function must be in access level 2. the manual VA reset can be

assigned to a button of an emergency microphone. Please refer to the software

manual for further details. If the emergency reset shall be made by an external

switch, then assign this function to a control input. the connection to the switch

should be monitored and the switch shall be put into access level 2.

the zone status is indicated by buttons assigned for zone selection on a remote

microphone. So assign the same VA zones or VA zone groups to zone selection

buttons as are available for the manual controls.

Table 4: Options requiring controls in access level 2

the options

- manual emergency activation,

- manual emergency phase shift,

- manual silencing of the voice alarm condition,

- faults of manually controlled VA zones (EN 54-16, §10.3)

must not be used because these are not certified yet. A certification is planned later.