beautypg.com

Sx link terminal connections, Sx link, Terminal – Toa SX-2000 Series Installation User Manual

Page 129: Connections

background image

129

4.5. SX Link Terminal Connections

connect the SX link terminals of all SX-2000Sm, SX-2000AI, SX-2100AI, SX-2000Ao, and SX-2100Ao units

within the system to each other via switching hubs. connect each of SX link terminals A and B to the same

switching hub or different switching hubs connected in star configuration.

Notes
• Make the SX Link terminals completely independent from other LAN.
• The distance between each of SX-2000SM, SX-2000AI, SX-2100AI, SX-2000AO, or SX-2100AO and a

switching hub, and between switching hubs is less than 100 m.

• Be sure to make connections of both terminals A and B.
• When using multiple switching hubs, make a star connection from the switching hub to which the SX-2000SM

is connected as shown in the example 2.

SX-2000SM

SX-2000AO (1)

SW-HUB

SW-HUB

SX-2000AO (2)

SW-HUB

SX-2100AI

SW-HUB

SX link A, B

SX link A, B

SW-HUB

SW-HUB

SX-2100AI

SX-2000AO

SW-HUB

SW-HUB

SX-2000SM

SW-HUB

SW-HUB

SW-HUB

SW-HUB

SX link B

SX link B

SX link A

SX link A

(Operating)

SX link B

(Operating)

SX link A

[Connection example 2: Non-redundant configuration of switching hubs]

[Connection example 1: Redundant configuration of switching hubs]

* A method of connecting a single unit's SX link A and B terminals to each different switching hub to prevent

the system from going down when a cable is broken or power fails.

This manual is related to the following products: