*Supplement
4.
Heat Dissipation
The type E and G Controllers are designed to be mounted inside of a control panel.
The air inside the panel must be cooled without external air exchange (Forced air current method or heat sink method).
Heat consumption and heat dissipation (for DC Type)
50mm or greater space
Super SEL
Fan 2
Fan 1
Heat exchanger
Example 2
Example 1
Mount base (metal
plate zinc coated)
Heat Consumption
Maximum
Heat Dissipation
60% Duty
35W
2 Axis
170W (rated)
30W (total load)
20W
60W
2 Axis
270W (rated)
50W (total load)
30W
100W
2 Axis
370W (rated)
70W (total load)
40W
200W
2 Axis
590W (rated)
100W (total load)
60W
For general use, the load duty is approximately 60%. However, for vertical axes which are constantly affected by the
weight of a load, greater heat dissipation must be taken into consideration.