*Supplement

4.

Heat Dissipation

 The type E and G Controllers are designed to be mounted inside of a control panel.

The air inside the panel must be cooled without external air exchange (Forced air current method or heat sink method).

‚ Heat consumption and heat dissipation (for DC Type)

50mm or greater space

Super SEL

Fan 2

Fan 1

Heat exchanger

Example 2

Example 1

Mount base (metal
plate zinc coated)

Heat Consumption

Maximum

Heat Dissipation

60% Duty

35W

2 Axis

170W (rated)

30W (total load)

20W

60W

2 Axis

270W (rated)

50W (total load)

30W

100W

2 Axis

370W (rated)

70W (total load)

40W

200W

2 Axis

590W (rated)

100W (total load)

60W

For general use, the load duty is approximately 60%. However, for vertical axes which are constantly affected by the
weight of a load, greater heat dissipation must be taken into consideration.