The external power supply, 9sa-pwex-000, General description, Hardware specifications – Verilink XEL XSP-100 SHARK IAP (9SA-USRS-9.0R1.02) Product Manual User Manual
Page 236: Electrical characteristics, Output voltage, Power output, Regulation, Hold-up time, Ripple & noise, Input

Chapter 9- Hardware Specifications
Chapter 9-36 XEL P/N & Release: 9SA-USRS-9.0R1.02 SHARK™ IAD User's Guide
The External Power Supply,
9SA-PWEX-000
100-249 VAC, 47-63 HZ to -48DC
G
ENERAL
DESCRIPTION
The external power supply is used in applications where -48DC is not available.
It can be placed on a table top or be wall mounted. It is used with the 9SA-
PW00-000 Internal Power Module.
H
ARDWARE
S
PECIFICATIONS
Output voltage:
-48 VDC
E
LECTRICAL
C
HARACTERISTICS
Power Output:
100 W maximum continuous, convection cooled
125 W Peak for 1 second
150 W peak for 0.1 second
Regulation:
Load:
± 1% maximum @ 20% to 100% of load and
nominal AC line.
± 2.5% maximum at o% load.
Line
± 1% maximum @ low to high line with
maximum rated load.
NOTE:
Regulation measured at end of properly terminated
6'/152mm DC output cable.
Longer cables may effect regulation.
Hold-up time:
12mS minimum @ rated load and nominal line
Ripple & noise
Does not Exceed 2% p/p of nominal output at rated
load.
Input:
100 -240VAC 47 - 63 HZ
Inrush Current:
20A @ 110v VAC with a cold unit. 40A @ 220 VAC
input.
E
NVIRONMENTAL
Operation Temp:
0° to 40° C, de-rated 25% at 50° C and 50% at 60° C
Humidity:
5% - 95% noncondensing
Altitude
0 to 10,000 feet
P
HYSICAL
C
HARACTERISTICS
Physical size
Width: 4"
Height: 3"
Length: 8"
Weight: 2.00 LB