Page 4-24
MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Pump Programming
Programming 8800 Series Units
Function Code 6 = Authorize After Stop
0 = Disabled (Default)
1 = Enabled
Function Code 7 = PRC Restore Option Programming
0 = Disabled (Default)
1 = Enabled
Command Code 2 - To Program the Unit to the Pulse Output Mode
Function Code 0 = Standard Mode
Function Code 1 = Two-wire Mode
Function Code 2 = Pulse Output Mode
Option and Miscellaneous Programming/Data Acquisition
Special programming is involved in ATC and displaying Totals.
ATC Programming
At power-up, the units programmed with the ATC option will flash 104 before displaying
normal information. Units with the option, but not programmed for ATC will flash 100. To
program the ATC option, proceed as follows:
1
Turn On the programming switch on the ATC Controller Board.
Note: The dispenser must not be used during this programming and all pump handles must be
down or inactive.
2
Press 100 on the keypad and then press Enter.
• The money position showing fueling position selected will display 1.
• The volume position showing the fuel type selected will display 1, where:
1 = Gasoline
2 = Diesel
• The PPU position showing fuel density selected will display 730, where:
740 = Gasoline
840 = Diesel
730 = Default
3
Select the fuel type and press Enter.
4
The firmware sequence will sequence through each fueling position. Select the fuel type for
each position (diesel or gasoline).
5
Turn the programming switch on the ATC controller board to Off.
6
Press F2 to exit the ATC Programming mode.