Measuring Pressure and Vacuum

Hydraulic/Mechanical Components

Pressure Measuring Locations on Unit

This section provides information about the pressure measuring locations on unit.

For Dispensers

Install the pressure gauge at any one of the following locations (see

Figure 6-7

):

To Check

Insert the Pressure Gauge in the

Inlet pressure (pressure available to dispenser)

Shear valve test port (location A)

Filter cap port pressure (pressure available at filter)

Special filter cap port fitting (location B)

Discharge pressure (pressure available to hanging
hardware)

Special discharge fitting (location C)

Figure 6-7: Typical Pressure Gauge Installations

20

30

0

60

10

50

40

20

30

0

60

10

50

40

20

30

0

60

10

50

40

Location B: Pressure
Gauge in Filter Cap Port

Special Discharge
T-fitting

Location C: Pressure Gauge in
Discharge Fitting

Location B: Pressure Gauge in
Shear Valve (Dispenser Only

Test Point

Measuring STP Pressure for Dispensers

To measure STP pressure for dispensers, proceed as follows:

1

Shut off power to the STP.

2

Verify if the dispenser and STP have been deactivated.

3

Always use eye protection. Install the gauge at the shear valve test port (see

Figure 6-7

),

Location A.

4

Turn on power to the STP.

5

Activate the handle. Do not pump fuel.