MDE-4334D Atlas™ Start-up and Service Manual · July 2013

Page 6-47

Hanging Hardware

Hydraulic/Mechanical Components

To test the hose and hanging hardware continuity, proceed as follows:

1

Ensure that there is no liquid fuel or flammable vapor present. Clean up, as required.

2

Lift the nozzle hook and authorize the unit to pressurize the hose.

3

Lower the nozzle hook, shutting the unit off.

Figure 6-24: Testing Hanging Hardware Continuity

Note: Use only a low voltage digital Ohmmeter to

perform this test. Do not use a Megger tester.

Digital Ohmmeter

Side Dispensing Unit

Front Dispensing Unit

A= Maintain at least 18 inches
above the ground and away from
the unit during the test

Note: When testing any unit, the A measurement of

18 inches applies whether the unit is a FRONT or
SIDE Dispensing unit.

A

A

Test Clip

Nozzle

Swivel

Breakaway

Outlet Casting

Test Clip

Hose