Warning – Gasboy Atlas Start-up User Manual
Page 221
MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Page 9-7
Preventive Maintenance Table
Preventive Maintenance and Inspection
Nozzles and boot
area
Once a week or
when notified about
a potential problem
1
Inspect nozzles for the following wear or damage:
• Damage
• Leaks
• Loose nozzle spouts
• Missing parts, such as retainer springs and splash guards
WARNING
Leaking fuel can be ignited, causing a fire or explosion.
Fire, explosion, or electrical shock could result in severe injury or death if you
continue to use damaged pumps/dispensers.
If you find any leaks or damage, stop using the pump/dispenser.
2
Inspect vapor recovery boots (bellows) for proper seal and damage.
3
Consult the nozzle manufacturer for additional inspections, if
required.
4
If repair is required, call an ASC to make the repairs.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal voltages.
Servicing a Gasboy Atlas unit incorrectly could result in severe injury or death.
Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy-trained ASCs must service a Gasboy Atlas unit.
• Owner - Inspect
• ASC only - Repair
and test
Leaks, external
Once a week or
when notified about
a potential leak
1
Inspect the following for any signs of damage or leaks, such as
cracks, cuts, wear, or flattening:
• Breakaways
• Couplings
• Hose outlet castings
• Hoses
• Nozzles
• Swivels
2
Review the documentation provided by the manufacturer of each
component.
3
If a leak is found, stop using the pump/dispenser and make
arrangements to repair the leak.
WARNING
Leaking fuel can be ignited, causing a fire or explosion.
Fire, explosion, or electrical shock could result in severe injury or death if you
continue to use damaged pumps/dispensers.
If you find any leaks or damage, stop using the pump/dispenser.
Leaks, external
(continued)
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal voltages.
Servicing a Gasboy Atlas unit incorrectly could result in severe injury or
death.
Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.
Components
Recommended
Frequency
Recommended Maintenance
Who Performs the
Inspection/Repair