beautypg.com

Warning – Gasboy Atlas Start-up User Manual

Page 222

background image

Preventive Maintenance and Inspection

Preventive Maintenance Table

Page 9-8

MDE-4334D Atlas™ Start-up and Service Manual · July 2013

Displays
(Electronic units)

Once a week

1

Inspect the displays for proper reading of all digits.

2

Verify if the displays are properly backlit.

• Owner - Inspect
• ASC only - Repair

and test

Breakaways

Once a week or after
drive-offs

1

Inspect breakaways for secure connections to the hose and for any

leaks.

2

For units with hose retrievers, position the breakaway coupling

between the retriever connection to the hose and the nozzle. The
breakaway whip hose must be attached to the nozzle.

3

For any additional required inspections, consult the breakaway

manufacturer.

4

If repair is required, call an ASC to make the repairs.

WARNING

Leaking fuel can be ignited, causing a fire or explosion.

Fire, explosion, or electrical shock could result in severe injury or death if you
continue to use damaged pumps/dispensers.

If you find any leaks or damage, stop using the pump/dispenser.

WARNING

The pump/dispenser contains pressurized flammable fuel and lethal voltages.

Servicing a Gasboy Atlas unit incorrectly could result in severe injury or death.

Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.

• Owner - Inspect
• ASC only - Repair

and test

Warning tags and
operating
instructions

Once a week

Inspect for and replace all missing, damaged, or unreadable warning tags
or operating instructions.

• Owner - Inspect
• Owner or ASC -

Replace

Hose continuity

Once a month

Verify if the hose continuity (including breakaway whip hose) complies
with the hose manufacturer’s requirements.

WARNING

Spilled fuel and fuel vapors may be present in or around the pump or
dispenser.

A spark can ignite the fuel or its vapors. Testing for hose continuity incorrectly
could result in severe injury or death. Refer to Petroleum Equipment Institute
PEI publication RP-500.

Use only approved methods and instruments. Do not allow untrained
personnel to service the Gasboy Atlas pumps/dispensers. Only Gasboy

Atlas-trained ASCs must service a Gasboy Atlas unit.

Hoses and end connections must be completely dry before checking for
continuity.

• ASC only - Inspect

and Repair

Components

Recommended
Frequency

Recommended Maintenance

Who Performs the