Important Requirements for E85 Units
Read This First
Important Requirements for E85 Units
Following equipment and materials are required to properly install E85 units:
UL-listed E85 Hose (Q13486)
• Veyance
SM
Flexsteel
™
Futura
®
Ethan-All for E85
• Veyance
Flexsteel Futura for E25
Note: Extended reach hoses are not available for E85 applications.
UL-listed E85 Nozzle (M11298)
OPW
®
21GE
Note: Approved for use with E85 dispensers, as required under UL 87A.
UL-listed E85 Swivel (N23748-04)
OPW 241 TPS-0492
Note: Approved for use with E85 dispensers, as required under UL 87A.
UL-listed E85 Shear Valve (T19695-23)
OPW 10P-0152E85
Note: Approved for use with E85 dispensers, as required under UL 87A.
UL-listed E85 Breakaway (N23010-10)
OPW 66V-0492
Note: Approved for use with E85 dispensers, as required under UL 87A.
Filter
Use only filters specifically marked for use with E85.
UL-listed Pipe Sealant
Use only UL-listed TPS PTFE Pipe Sealant manufactured by SAF-T-LOC International Corp.
UL-listed Teflon
®
Tape
Use only UL-listed Taega Technologies Inc. Teflon tape.
Note: Teflon tape must be used only at the inlet pipe connection.
CAUTION
Certain special alternative fuels such as E85 and additives can degrade pump/dispenser
performance or integrity, if the dispensers are not designed for use with such fuels. Additionally,
converting to certain standard fuels (gasoline, diesel, kerosene, and so on) from alternative fuels
such as those with ethanol (E85), methanol, or biodiesel or from alternative fuels to standard fuels
can degrade dispenser performance or integrity. Similar effects can also occur when converting units
to different standard fuel types. As per UL 87A requirements, units dispensing E85 fuel must not
be used to dispense any other type of fuel such as Gasoline.
Leaks and potential environmental hazards can result or components may fail prematurely.
To avoid these issues, follow the guidelines in this section.