Preventive Maintenance Table

Preventive Maintenance and Inspection

Leaks, internal

Once a month, after
a drive off, or as
notified about a
potential leak

1

Whenever possible, Gasboy recommends shutting off power to the

unit before performing these inspections.

2

Block off the pump/dispenser to prevent customers from operating

the pump/dispenser during inspection.

3

Remove the lower panels slowly and carefully.

4

Inspect all hydraulic connections and seals, including the following:
• Meters
• Valves

5

If wetness or dripping fuel is found, stop using the pump/dispenser,

and make arrangements for repairing the leak.

Note: Some staining of parts around seals is normal and does not

necessarily indicate a leak.

6

Monitor the repaired components closely during subsequent

inspections.

WARNING

Gasoline or other fuels can damage the eyes.

Fuel sprayed into the eye can burn the eye tissue.

To prevent potential injury, wear eye protection when performing these
inspections.

• Owner - Inspect
• ASC only - Repair

and test

Leaks, internal
(continued)

WARNING

Leaking fuel can be ignited, causing a fire or explosion.

Fire, explosion, or electrical shock could result in severe injury or
death if you continue to use damaged pumps/dispensers.

If you find any leaks or damage, stop using the pump/dispenser.

WARNING

The pump/dispenser contains pressurized flammable fuel and lethal voltages.

Servicing a Gasboy Atlas unit incorrectly could result in severe injury or
death.

Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.

Filter change and
strainer cleaning

New Installations -
After 50,000 gallons
(200,000 liters), or
after one month

After the first filter
change - Every
300,000 gallons
(1.0 million liters),
every six months, or
when the fuel
delivery rate
significantly slows

Replace the filters and clean the strainers regularly. An ASC must
perform these tasks. DEF strainers must be cleaned after purging and
calibration during start-up. Else, clean when the flow rate drops
noticeably. Replace strainers that are permanently clogged.

The pump/dispenser contains pressurized flammable fuel and lethal voltages.

Servicing a Gasboy Atlas unit incorrectly could result in severe injury or death.

Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.

WARNING

Components

Recommended
Frequency

Recommended Maintenance

Who Performs the
Inspection/Repair