Page 4-8

MDE-4334D Atlas™ Start-up and Service Manual · July 2013

Pump Programming

Configuring 9800 Series

Pulse Output Rate Switches (If JP2 on M06333KXXXX CPU is Jumpered or SW1-2 on
Previous CPU is Closed)
When the pump/dispenser is connected to an external controlling equipment other than CFN
System, Fleet Plus System, or TopKAT Electronic System, that requires pulse output signals
(for example, Pulse-out I/F configuration interfacing with Gasboy Series 1000 and

non-Gasboy systems), the pulse signals are sent through the Pulse-out Interface Board. Setting
switches SW2-1 through SW2-3 configures the Pulse-out rate required by the monitoring
equipment. The Pulse-out rate represents the pulses per unit (gallon, liter, or imperial gallon).
SW2 may require to be sealed by a W&M paper seal if the unit is used for resale of the
product.

Pulse Rate

SW2-1

SW2-2

SW2-3

1:1

Closed

Closed

Closed

10:1

Open

Closed

Closed

100:1

Closed

Open

Closed

250:1

Open

Open

Closed

500:1

Closed

Closed

Open

None

Open

Closed

Open

None

Closed

Open

Open

None

Open

Open

Open

The maximum pulse output rate that can be achieved depends on the model of the
pump/dispenser and the unit of measure. Pulse output rate of 1000:1 is not supported.

Address

SW2-1

SW2-2

SW2-3

SW2-4

1

Closed

Closed

Closed

Closed

2

Open

Closed

Closed

Closed

3

Closed

Open

Closed

Closed

4

Open

Open

Closed

Closed

5

Closed

Closed

Open

Closed

6

Open

Closed

Open

Closed

7

Closed

Open

Open

Closed

8

Open

Open

Open

Closed

9

Closed

Closed

Closed

Open

10

Open

Closed

Closed

Open

11

Closed

Open

Closed

Open

12

Open

Open

Closed

Open

13

Closed

Closed

Open

Open

14

Open

Closed

Open

Open

15

Closed

Open

Open

Open

16

Open

Open

Open

Open