Servicing pressure control valve (pcv), Servicing pressure control valve (pcv) -54 – Gasboy Atlas Start-up User Manual
Page 174
Page 6-54
MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Hydraulic/Mechanical Components
Pumping Unit
Servicing Pressure Control Valve (PCV)
This section explains about servicing the pressure control valve.
Removing PCV
The purpose of the PCV is to apply a slight back pressure to the pumping unit, to prevent it
from pumping air through the meter (for example, during a dry tank situation). Meters will
meter air as well as fluid.
Excessive wear or a sticking PCV can cause improper pump performance, including flow loss,
excessive or low discharge pressure, or metering of air under a dry tank condition.
To remove a PCV, proceed as follows:
1
Drain the pumping unit. Refer to
2
Remove the snap ring (see
Figure 6-29: PCV
3
Turn the valve cover outward or counterclockwise using a 16 mm socket wrench until it is
completely removed.
Note: The cover is held on by bolts and not screwed in.
4
Remove the spring and valve.
5
Remove the valve from the bore using needle nose pliers.