beautypg.com

Warning – Gasboy Atlas Start-up User Manual

Page 225

background image

MDE-4334D Atlas™ Start-up and Service Manual · July 2013

Page 9-11

Preventive Maintenance Table

Preventive Maintenance and Inspection

Nozzle hooks and
shafts

Every six months

1

Lubricate with silicone spray, if required.

2

Check for damage.

3

Verify if the locking tab locator is not broken (The locking tab locator

helps hold the nozzle in the nozzle boot and enables the station
owner to lock the nozzle boot with a clasp padlock).

4

If repair is required, call an ASC to make the repairs.

5

An ASC must make any required repairs.

WARNING

The pump/dispenser contains pressurized flammable fuel and lethal voltages.

Servicing a Gasboy Atlas unit incorrectly could result in severe injury or death.

Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.

• Owner - Inspect
• ASC only - Repair

and test

Mechanical
computers

Every six months

Lubricate well. Refer to Veeder-Root manuals for lubrication
points.

WARNING

The pump/dispenser contains pressurized flammable fuel and lethal voltages.

Servicing a Gasboy Atlas unit incorrectly could result in severe injury or death.

Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.

ASC only

Door locks

Every six months or
if the door locks
become difficult to
open and close

Lubricate with a graphite lubricant or lock oil. Follow the manufacturer’s
instructions. Do not over-lubricate. Use a rag to wipe any excess lubricant
that may drip.

Owner

Tank

Every month

Monitor water levels in the tank with an electronic tank monitor or water
detection pasted on the tank measuring stick.

Owner - Inspect

Water in
dispenser/Pit box

After every fuel tank
fill-up

Remove with explosion proof sump pump.
1

Gasboy recommends shutting off power to the unit before performing

these inspections and process.

2

Block off the pump/dispenser to prevent customers from operating

the pump/dispenser during procedure.

3

Access and insert the sump pump into the tank and draw off the

water.

WARNING

The water in the pit box could contain gasoline or a flammable fluid.

Use of an electrical pump directly in the pit box could result in a fire or
explosion.

Do not use an electrical pump unless explosion proof. A mechanical hand
pump is recommended.

• Owner - Inspect
• ASC only - Repair

and test

Components

Recommended
Frequency

Recommended Maintenance

Who Performs the
Inspection/Repair