Warning – Gasboy Atlas Start-up User Manual
Page 225
MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Page 9-11
Preventive Maintenance Table
Preventive Maintenance and Inspection
Nozzle hooks and
shafts
Every six months
1
Lubricate with silicone spray, if required.
2
Check for damage.
3
Verify if the locking tab locator is not broken (The locking tab locator
helps hold the nozzle in the nozzle boot and enables the station
owner to lock the nozzle boot with a clasp padlock).
4
If repair is required, call an ASC to make the repairs.
5
An ASC must make any required repairs.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal voltages.
Servicing a Gasboy Atlas unit incorrectly could result in severe injury or death.
Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.
• Owner - Inspect
• ASC only - Repair
and test
Mechanical
computers
Every six months
Lubricate well. Refer to Veeder-Root manuals for lubrication
points.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal voltages.
Servicing a Gasboy Atlas unit incorrectly could result in severe injury or death.
Do not allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs must service a Gasboy Atlas unit.
ASC only
Door locks
Every six months or
if the door locks
become difficult to
open and close
Lubricate with a graphite lubricant or lock oil. Follow the manufacturer’s
instructions. Do not over-lubricate. Use a rag to wipe any excess lubricant
that may drip.
Owner
Tank
Every month
Monitor water levels in the tank with an electronic tank monitor or water
detection pasted on the tank measuring stick.
Owner - Inspect
Water in
dispenser/Pit box
After every fuel tank
fill-up
Remove with explosion proof sump pump.
1
Gasboy recommends shutting off power to the unit before performing
these inspections and process.
2
Block off the pump/dispenser to prevent customers from operating
the pump/dispenser during procedure.
3
Access and insert the sump pump into the tank and draw off the
water.
WARNING
The water in the pit box could contain gasoline or a flammable fluid.
Use of an electrical pump directly in the pit box could result in a fire or
explosion.
Do not use an electrical pump unless explosion proof. A mechanical hand
pump is recommended.
• Owner - Inspect
• ASC only - Repair
and test
Components
Recommended
Frequency
Recommended Maintenance
Who Performs the
Inspection/Repair