Purging Air from System
Hydraulic/Mechanical Components
Self-contained Pumping Units
Recommended Torque
Unit
in-lbs
Nm
Pump head (tightened in star pattern)
200
23
Strainer cover
150
17
Rear cover
200
23
Meter Bolts
Recommended Torque
Bolt (In Order)
in-lbs
Kg-meters
1
Cylinder cover gasket
130 ± 10
1.50 ± 0.12
2
Piston and connecting bar
35 ± 5
0.40 ± 0.06
3
Shaft seal cap
25 ± 5
0.30 ± 0.06
4
Lower bearing housing
75 ± 10
0.90 ± 0.12
5
Packing retainer
20 ± 5
0.25 ± 0.06
6
Body cover
130 ± 10
1.50 ± 0.12
Purging Air from System
• Wear eye protection. Residual pressure and entrapped fuel may still be present
and may drain or spray while removing the parts.
• Fire and explosion could result in severe injury or death.
• Test and close the involved shear valves. Shut off power to the unit.
• Remove the parts slowly. Collect fuel in approved containers.
• Clean up all spills promptly.
WARNING
About Purging System
Purge air from the hydraulic system properly. Failure to properly purge air from the system
can damage components and result in inaccurate calibration and fuel delivery. Purge air from
the system for new installations or when fluid containing parts of the hydraulic system are
serviced.