Atc setup, Atc setup -10, Setting dip switches – Gasboy Atlas Start-up User Manual
Page 42: This switch must be open for normal operation, This switch is not used. set to the open position

Page 4-10
MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Pump Programming
Configuring 9800 Series
SW2-8 - Background Debug Module (BDM) Enable (Only on
M06333KXXXX CPU)
This switch must be OPEN for normal operation.
SW2-9 - Software Load Enable (Only on M06333KXXXX CPU)
This switch must be OPEN for normal operation. When this switch is closed, it enables lo
ading the new M06333KXXXX CPU software.
SW2-10 (Only on M06333KXXXX CPU)
This switch is not used. Set to the Open position.
ATC Setup
When you activate the magnet located at the opposite side of the totalizer, following items
appear on the display:
Display Name
Example Display Description
Volume
0023043
Uncompensated volume
Probe Temperature
023.2
Probe temperature in Celsius only
Flow Rate
189.2
Flow rate (in LPM only)
Software Version
1.30
Software version number
ATC Status
842.2
Automatic Temperature Compensation
On the status display, the rightmost digit (2) indicates whether the temperature compensation
is enabled or not, and if so, the product that is being dispensed. Following digits indicate the
settings that have been enabled:
• 0 = Temperature compensation enabled
• 1 = Product is gasoline and compensation is enabled
• 2 = Product is diesel and compensation is enabled
On the status display, the leftmost digits (842) are error indicators, which are blank when the
corresponding error condition is not active. When any of these digits are displayed, it indicates
the following:
• 8 = Temperature probe fault is detected
• 4 = Pulser error occurred
• 2 = Exceptional reset was detected
Setting DIP Switches
DIP Switch Settings
Switch
Number Switch Function
Settings for Existing and Model 9850K
Settings for Models 9840K,
9852K, 9853K
1
Product 1
ON for Diesel, OFF for Gasoline
ON for Diesel, OFF for
Gasoline
2
Product 2
ON for Diesel, OFF for Gasoline
ON for Diesel, OFF for
Gasoline
3
Not Used
N/A
N/A
4
Unit of Measure
N/A
ON for Liters, OFF for Gallons
5
Pulser Multiplier
ON for 9850 and 9850K, OFF for 9852/9853
N/A
6
Number of Probes
ON for two (2) probes, OFF for one (1) probe ON for two (2) probes, OFF for
one (1) probe