MDE-4334D Atlas™ Start-up and Service Manual · July 2013

Page 6-45

Hanging Hardware

Hydraulic/Mechanical Components

4

Check for damage to the nozzle, especially the spout and threads.

5

If the repair or replacement is the result of a drive-off, inspect the unit for structural, meter, and
piping damage. Repair or replace the damaged components, as required.
Note: Meters, piping, and connections may leak after a drive-off.

6

Replace the breakaway if it is not of the reusable type.

7

Restore power to the unit and open the shear valves.

8

Authorize the nozzle and check for leaks in the hose and plumbing, especially the meter and
filter.

9

Purge the system of air. For more information, refer to

“Purging Air from System”

on

page 6-9

.

10

Perform a hose continuity test. Refer to

“Testing Hose and Hanging Hardware Continuity”

on

page 6-46

.

Resetting Breakaways

Note: Not all breakaways can be reset. Consult the supplier or manufacturer of the breakaway

used.

To reset a breakaway, proceed as follows:

1

Close and test the shear valve. The unit may require multiple shear valve closures. Also, refer
to the manufacturer’s instructions.

2

Shut off power to the unit and associated STPs. Use OSHA lockout/tagout procedures.

3

Check for damage to the nozzle, especially the spout and threads.

4

If the repair or replacement is the result of a drive-off, inspect the unit for structural, meter, and
piping damage. Repair or replace the damaged components, as required.
Note: Meters, piping, and connections may leak after a drive-off.

5

Check for damage to the breakaway valve and seals before reassembly. Follow the
manufacturer’s instructions.

6

Follow the manufacturer’s instructions for cleaning and lubricating seals and valve ends.

7

Follow the manufacturer’s instructions for recoupling.

8

Restore power to the unit and open shear valves.

9

Authorize the nozzle and check for leaks in the hose and plumbing, especially the meter and
filter.

10

Purge the system of air. For more information, refer to

“Purging Air from System”

on

page 6-9

.

11

Perform a hose continuity test. Refer to

“Testing Hose and Hanging Hardware Continuity”

on

page 6-46

.