Gasboy Atlas Start-up User Manual
Page 55
MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Page 4-23
Programming 8800 Series Units
Pump Programming
Command Code 17 - Conversion Factor and Master Reset Select
Function
The Conversion Factors/Performing Master Resets function is normally used during the setup
of a unit, to program the unit of measure and provide a means to do a firmware initiated Master
Reset.
Function Code 1: Conversion Factor
0 = No conversion factor*
1 = US. Gallons
2 = Imperial Gallons
3 = Liters
4 = 1012 Pulses per gallon
Function Code 2: Master Reset
0 = No Master Reset
1 = Master Reset
Command Code 18 - To Program Various Options Under Pulse Output
Function Code 1 = Volume Pulses per Unit
1 = 1
2 = 10 (Default)
3 = 50
4 = 100
5 = 1000
Function Code 2 = Volume Output Pulse Width
1 = 0.5 ms
2 = 1.0 ms
3 = 2.0 ms
4 = 4.0 (Default)
5 = 17.0 ms
6 = 19.0 ms
7 = 26.0 ms
8 = 150.0 ms
Function Code 3 = Money Output Pulse Width
1 = 0.5 ms
2 = 1.0 ms
3 = 2.0 ms
4 = 4.0 (Default)
5 = 17.0 ms
6 = 19.0 ms
7 = 26.0 ms
Function Code 4 = Volume Suppression
1 = 0.030 (Default)
2 = 0.009
3 = 0.000
Function Code 5 = Quadrature Pulse Output
0 = Disabled (Default)
1 = Enabled