Programming steps for 8800 series units, Level 1 programming – Gasboy Atlas Start-up User Manual
Page 47
MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Page 4-15
Programming 8800 Series Units
Pump Programming
Programming Steps for 8800 Series Units
This section provides the programming steps for 8800 Series units.
Master Reset/Warmstart
A Master Reset removes all programming, unit configuration, and dispenser memory in
addition to resetting the internal processor to an initial state. It is frequently referred to as a
Cold Start. A Warmstart (power-down and up of the unit) only resets the processor to an initial
state.
Master Resets are generally required:
• When changing the software
• To temporarily or permanently fix a locked dispenser or unusual dispenser response
A Master Reset is a powerful service tool. However, when troubleshooting a non-responsive
pump, avoid performing a Master Reset as the first step in troubleshooting. First observe the
symptoms, observe the diagnostic LEDs, and check the voltage, as appropriate. In many cases,
a Master Reset will hide problems that are being alerted by these troubleshooting aids by
resetting the pump/dispenser processor. If multiple or repetitive resets are required, investigate
a hardware or software issue.
To perform a Master Reset, proceed as follows:
1
Record all totals and programming. Isolate the unit at the D-Box.
2
Turn off power to the unit.
3
Install a jump jack on JP-1B on the A side main display (J-box opening side).
4
Restore power to the unit and wait for Error Code 40.
5
Remove the jump jack.
6
Reprogram the unit.
7
Bring the unit back on line at the D-Box.
Level 1 Programming
Following information gives specific programming steps for Level 1 commands. All this
information is entered on the Manager Keypad. Ensure that you follow the following steps.
The side with the J-box opening is Side 1 while the other side is Side 2. Power-up and
Command Code 8 will display the current software version.
For Level 1 programming, proceed as follows:
1
Press Fl.
2
Enter the 4-digit ID (default 2222) and then press Enter.
3
Press F1 to exit any command code.
4
Press F2 to return to normal operation.
You may enter any command code directly from Level 1 after entering the PIN code.