Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-49

The parameter determines how the motor is stopped when the AC motor drive receives a valid

stop command.

Operation
Command

Operation

Command

Time

Time

Free running

to stop

Output

Frequency

RUN

STOP

RUN

STOP

Output

Frequency

Ramp to stop: the AC motor drive decelerates from the maximum output frequency (Pr. 01-
00) to minimum output frequency (Pr. 01-09) according to the deceleration time and then
stop.

Coast to stop: the AC motor drive stops the output instantly upon a STOP command and
the motor free runs until it comes to a complete standstill.

(1) It is recommended to use “ramp to stop” for safely of personnel or to prevent material
from being wasted in applications where the motor has to stop after the drive is stopped.
The deceleration time has to be set accordingly.

(2) If the motor free running is allowed or the load inertia is large, it is recommended to
select “coast to stop”. For example, blowers, punching machines and pumps.

The stop method of the torque control is also set by Pr.00-22.



00-23

Reverse Operation

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory setting: 0

Settings

0

Enable

reverse

1

Disable reverse

2

Disable forward

This parameter enables the AC motor drives to run in the Reverse Direction. It may be used to

prevent a motor from running in a direction that would consequently injure humans or damage

the equipment.