beautypg.com

Group 11 advanced parameters – Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 74

background image

Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-25

Group 11 Advanced Parameters

Pr.

Explanation

Settings

Factory

Setting

VF VFPG SVC FOCPG TQRPG

11-00 System Control

bit 0: ASR Auto tuning
bit 1: Inertia estimate (only for FOCPG mode)
bit 2: Zero Servo
bit 3: Reserved
bit 4: Enable gain adjustment of position loop KP

0 ○

11-01

Per Unit of System
Inertia

1~65535 (256=1PU)

400

11-02 Low-speed Bandwidth 0~40Hz 10

11-03 High-speed Bandwidth 0~40Hz 10

11-04 PDFF Gain Value

0~200% 30

11-05

Gain Value of Flux
Weakening Curve for
Motor 1

0~200% 90

11-06

Gain Value of Flux
Weakening Curve for
Motor 2

0~200% 90

11-07

Detection Time for
Phase-loss

0.01~600.00 sec

0.20

11-08

Reserved

11-09 Level of Phase-loss

0.0~320.0 60.0

11-10

Speed Feed Forward
Gain

0~100% 0

11-11 Zero-speed Bandwidth 0~40Hz 10

11-12

Speed Response of
Flux Weakening Area

0: Disable
0~150%

65 ○

11-13 Notch Filter Depth

0~20db 0

11-14 Notch Filter Frequency 0.00~200.00 0.00

11-15

Gain Value of Slip
Compensation

0.00~1.00 1.00

11-16

Low-pass Filter Time
of Keypad Display

0.001~65.535sec 0.100

11-17

Low-pass Filter Time
of PG2 Pulse Input

0.000~65.535sec 0.100

11-18 APR Gain

0.00~40.00 10.00

11-19 APR Curve Time

0.00~655.35 sec

3.00

11-20

|

11-28

Reserved

11-29

Accumulative
Operation Time of
Phase-loss

0~65535 (hour)

0

11-30

|

11-40

Reserved