Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-111

07-10

Base Block Speed Search

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Stop

operation

1

Speed search starts with last frequency command

2

Speed search starts with minimum output frequency

This parameter determines the AC motor drive restart method after External Base Block is

enabled.

In PG control mode, the AC motor drive will execute the speed search function automatically

by the PG speed when this setting isn’t set to 0.

07-11

Auto Restart After Fault

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0 to 10

Only after an over-current OC or over-voltage OV fault occurs, the AC motor drive can be

reset/restarted automatically up to 10 times.

Setting this parameter to 0 will disable the reset/restart operation after any fault has occurred.

When enabled, the AC motor drive will restart with speed search, which starts at the frequency

before the fault. To set the waiting time before restart after a fault, please set Pr. 07-08 Base

Block Time for Speed Search.

07-12

Speed Search during Start-up

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Disable

1

Speed search from maximum frequency

2

Speed search from start-up frequency

3

Speed search from minimum frequency

This parameter is used for starting and stopping a motor with high inertia. A motor with high

inertia will take a long time to stop completely. By setting this parameter, the user does not

need to wait for the motor to come to a complete stop before restarting the AC motor drive. If a

PG card and encoder is used on the drive and motor, then the speed search will start from the

speed that is detected by the encoder and accelerate quickly to the commanded frequency.

The output current is set by the Pr.07-09.