Group 11 Advanced Parameters

11-00

System Control

Control

mode

FOCPG

Factory Setting: 0

Settings

Bit 0 ASR Auto tuning

Bit 1 Inertia estimate (only in FOCPG mode)

Bit

2

Zero

Servo

Bit

3

Reserved

Bit 4 Enable gain adjustment of position loop KP

Bit 0=1: system will generate an ASR setting and Pr. 10-04~10-07, 10-21~10-22 will be invalid.

Bit 1=1: Inertia estimate function is enabled.

Bit 2=1: when frequency command is less than Fmin (Pr.01-07), it will use zero servo function.

YES

NO

Estimate Jm value

Setting auto gain adjustment

Pr.11-00=1

Adjust Pr.11-02, 11-03 and 11-11

separately by speed response

Adjust by requirement
Pr.11-04 (PDFF function)

Adjust by requirement

Pr.10-08
(ASR1/ASR2 switch frequency)

Adjust by requirement
Pr.07-32~35 (torque limit)

Adjust gain value by manual
Pr.11-00=0 (factory setting)

Adjust Pr.10-04, 10-05, 10-06,
10-07, 10-21 and 10-22

separatelyby speed response

Adjust by requirement
Pr.10-09 (for general,