Chapter 4 Parameters|

4-122

Revision August 2008, 03VE, SW V2.04

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.0

Settings

0.0 to 3600.0 sec

This parameter defines the time during which the PID feedback must be abnormal before a

warning is given. It also can be modified according to the system feedback signal time.

If this parameter is set to 0.0, the system would not detect any abnormality signal.

08-09

Feedback Fault Treatment

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0

Settings

0

Warn and keep operating

1

Warn and RAMP to stop

2

Warn and COAST to stop

3

Warn and keep at last frequency

AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder)

feedback) are abnormal.

08-10

Sleep Frequency

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.00

Settings

0.00 to 600.00Hz

08-11

Wake-up Frequency

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.00

Settings

0.00 to 600.00Hz

08-12

Sleep Time

Unit: 0.1

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.0

Settings

0.0

to

6000.0sec

These parameters determine sleep functions of the AC drive. If the command frequency falls

below the sleep frequency, for the specified time in Pr. 08-12, then the drive will shut off the

output and wait until the command frequency rises above Pr. 08-11. Please see the below

diagram.