Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-95

Group 6 Protection Parameters

06-00

Low Voltage Level

Unit: 0.1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Settings 230V series 160.0~220.0Vdc

Factory Setting: 180.0

460V series 320.0~440.0Vdc

Factory Setting: 360.0

It is used to set the Lv level.

LV

Pr. 06-00

30V(60V)

input voltage

06-01

Over-Voltage Stall Prevention

Unit: 0.1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Settings 230V series 350.0~450.0Vdc

Factory Setting: 380.0

460V series 700.0~900.0Vdc

Factory Setting: 760.0

0.0: disable (when brake resistor used)

During deceleration, the DC bus voltage may exceed its Maximum Allowable Value due to

motor regeneration. When this function is enabled, the AC motor drive will not decelerate

further and keep the output frequency constant until the voltage drops below the preset value

again.

output
frequency

Deceleration characteristic
when Over-Voltage Stall

Prevention enabled

Frequency Held

time

previous

deceleration time