2.3.2 Main Circuit Terminals

Frame B

+1

+2 B

1

-

B

2

U/T1 V/T2 W/T3

Screw Torque :

Wire Gauge :

18Kgf-cm

18~10AWG

R/L1 S/L2 T/L3

Main circuit terminals

R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,

, +1, +2/B1, -, B2

Models

Wire

Torque

Wire Type

VFD007V23A-2

VFD007V43A-2

VFD015V23A-2

VFD015V43A-2

VFD022V23A-2

VFD022V43A-2

VFD037V23A-2

VFD037V43A-2

14-10 AWG

(2.1-5.3mm

2

)

18kgf-cm

(15.6in-lbf)

Stranded

copper only,

75

o

C

Frame C

POWER

IM

MOTOR

3


Main circuit terminals

R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,

, +1, +2/B1, -, B2

Models

Wire

Torque

Wire Type

VFD055V23A-2

VFD075V23A-2

VFD110V43B-2

VFD055V43A-2

VFD075V43A-2

12-8 AWG

(3.3-8.4mm

2

)

30kgf-cm

(26in-lbf)

Stranded

copper only,

75

o

C