Chapter 4 Parameters|

4-140

Revision August 2008, 03VE, SW V2.04

DATA (n-1)

to

DATA 0

Contents of data:
Nx8-bit data consist of 2n ASCII codes
n<=16, maximum of 32 ASCII codes

LRC CHK Hi

LRC CHK Lo

LRC check sum:
8-bit check sum consists of 2 ASCII codes

END Hi

END Lo

End characters:
END1= CR (0DH), END0= LF(0AH)

RTU mode:

START

A silent interval of more than 10 ms

Address

Communication address: 8-bit address

Function

Command code: 8-bit command

DATA (n-1)

to

DATA 0

Contents of data:
n

×8-bit data, n<=16

CRC CHK Low

CRC CHK High

CRC check sum:
16-bit check sum consists of 2 8-bit characters

END

A silent interval of more than 10 ms

3.2 Address (Communication Address)

Valid communication addresses are in the range of 0 to 254. A communication address equal to 0,

means broadcast to all AC drives (AMD). In this case, the AMD will not reply any message to the
master device.

00H: broadcast to all AC drives

01H: AC drive of address 01
0FH: AC drive of address 15
10H: AC drive of address 16
:
FEH: AC drive of address 254

For example, communication to AMD with address 16 decimal (10H):
ASCII mode: Address=’1’,’0’ => ‘1’=31H, ‘0’=30H

RTU mode: Address=10H

3.3 Function (Function code) and DATA (data characters)

The format of data characters depends on the function code.

03H: read data from register
06H: write single register
08H: loop detection
10H: write multiple registers
The available function codes and examples for VFD-VE are described as follows:

(1) 03H: multi read, read data from registers.

Example: reading continuous 2 data from register address 2102H, AMD address is 01H.

ASCII mode:

Command message:

Response message:

STX ‘:’

STX ‘:’

‘0’

‘0’

Address

‘1’

Address

‘1’

‘0’

‘0’

Function

‘3’

Function

‘3’

‘2’

‘0’

Starting data

address

‘1’

Number of data

(Count by byte)

‘4’