Group 10 PID Control

10-00

Encoder Pulse

Unit: 1

Control

mode

VFPG

FOCPG

TQRPG

Factory Setting: 600

Settings

1 to 20000 (Max=20000 for 2-pole motor)

A Pulse Generator (PG) or encoder is used as a sensor that provides a feedback signal of the

motor speed. This parameter defines the number of pulses for each cycle of the PG control.

10-01

Encoder Input Type Setting

Control

mode

VFPG

FOCPG

TQRPG

Factory Setting: 0

Settings 0

Disable

1

Phase A leads in a forward run command and phase B leads in a
reverse run command

A

B

FWD

REV

2

Phase B leads in a forward run command and phase A leads in a
reverse run command

A

B

FWD

REV

3

Phase A is a pulse input and phase B is a direction input. (low
input=reverse direction, high input=forward direction)

A

B

FWD

REV

4

Phase A is a pulse input and phase B is a direction input. (low
input=forward direction, high input=reverse direction)

A

B

FWD

REV

5

Single-phase input

A

It is helpful for the stable control by inputting correct pulse type.