beautypg.com

Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 235

background image

Chapter 6 Fault Code Information and Maintenance|

6-10

Revision August 2008, 03VE, SW V2.04

„

DC capacity of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there is any leak of liquid,
color change, crack or
deformation

Visual inspection

{

Measure static capacity when
required

Static capacity

initial value X 0.85

{

„

Resistor of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there is any peculiar smell or
insulator cracks due to overheat

Visual inspection, smell

{

If there is any disconnection

Visual inspection or measure with
multimeter after removing wiring
between +1/+2 ~ -
Resistor value should be within

±

10%

{

„

Transformer and reactor of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there is any abnormal vibration
or peculiar smell

Visual, aural inspection and smell

{

„

Magnetic contactor and relay of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there are any loose screws

Visual and aural inspection

{

If the contact works correctly

Visual inspection

{