beautypg.com

Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 31

background image

Chapter 2 Installation and Wiring|

2-8

Revision August 2008, 03VE, SW V2.04

„

To improve power factor and reduce harmonics connect a DC reactor between terminals

[+1, +2]. Please remove the jumper before connecting the DC reactor.

NOTE

Models of 15kW and above have a built-in DC reactor.

Terminals [+2/B1, B2] for connecting brake resistor and terminals [+1, +2/B1] for

connecting external brake unit

Brake unit(optional)
Refer to Appendix B for the use of

spec ial braking resis tor/unit

+2/B1

B2

BR

+2/B1

-

VFDB

BR

Brake resistor(optional)

„

Connect a brake resistor or brake unit in applications with frequent deceleration ramps,

short deceleration time, too low brake torque or requiring increased brake torque.

„

If the AC motor drive has a built-in brake chopper (all models of 11kW and below),

connect the external brake resistor to the terminals [+2/B1, B2].

„

Models of 15kW and above don’t have a built-in brake chopper. Please connect an

external optional brake unit (VFDB-series) and brake resistor. Refer to VFDB series user

manual for details.

„

Connect the terminals [+(P), -(N)] of the brake unit to the AC motor drive terminals

[+2(+2/B1), (-)]. The length of wiring should be less than 5m with twisted cable.

„

When not used, please leave the terminals [+2/B1, -] open.

WARNING!

1.

Short-circuiting [B2] or [-] to [+2/B1] can damage the AC motor drive.


Grounding terminals (

)

„

Make sure that the leads are connected correctly and the AC drive is properly grounded.

(Ground resistance should not exceed 0.1Ω.)

„

Use ground leads that comply with local regulations and keep them as short as possible.

„

Multiple VFD-VE units can be installed in one location. All the units should be grounded

directly to a common ground terminal, as shown in the figure below. Ensure there are no

ground loops.

good

excellent

not allowed