background image

Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-145

Content Address

Function

Bit 0

1: EF (external fault) on

Bit 1

1: Reset

Bit 2

1: B.B. ON

2002H

Bit 3-15

Reserved

2100H

Error code: refer to Pr.06-17 to Pr.06-22
Bit 0

1: FWD command

Bit 1

1: Operation status

Bit 2

1: Jog command

Status

monitor

Read only

2119H

Bit 3

1: REV command

Bit 4

1: REV command

Bit 8

1: Master frequency Controlled by communication

interface

Bit 9

1: Master frequency controlled by analog signal

Bit 10

1: Operation command controlled by

communication interface

Bit 11

1: Parameters have been locked

Bit 12

1: enable to copy parameter from keypad

Bit 13-15

Reserved

2102H

Frequency command (F)

2103H

Output

frequency

(H)

2104H

Output

current

(AXXX.X)

2105H

DC-BUS Voltage (UXXX.X)

2106H

Output voltage (EXXX.X)

2107H

Current step number of Multi-Step Speed Operation

2109H

Counter

value

2116H

Multi-function display (Pr.00-04)

211AH

Setting

frequency

(F)

211BH

Max. setting frequency

211CH

Max.

output

frequency

2200H

Feedback Signal (XXX.XX %)

2203H

AVI analog input (XXX.XX %)

2204H

ACI analog input (XXX.XX %)

2205H

AUI analog input (XXX.XX %)

2206H

Display temperature of IGBT (

o

C)

2207H

Display temperature of heatsink (

o

C)

3.6 Exception response:

The AC motor drive is expected to return a normal response after receiving command messages

from the master device. The following depicts the conditions when no normal response is replied to
the master device.

The AC motor drive does not receive the messages due to a communication error; thus, the AC

motor drive has no response. The master device will eventually process a timeout condition.

The AC motor drive receives the messages without a communication error, but cannot handle them.

An exception response will be returned to the master device and an error message “CExx” will be
displayed on the keypad of AC motor drive. The xx of “CExx” is a decimal code equal to the
exception code that is described below.

In the exception response, the most significant bit of the original command code is set to 1, and an

exception code which explains the condition that caused the exception is returned.


Example of an exception response of command code 06H and exception code 02H:

ASCII mode:

RTU mode: