Chapter 4 Parameters|

4-94

Revision August 2008, 03VE, SW V2.04

Pr.05-26 to Pr.05-28 are used to set allowable slip level/time and over slip treatment when the

drive is running.

05-29

Hunting Gain

Unit: 1

Control

mode

VF

VFPG

SVC

Factory setting: 2000

Settings

0 to 10000 (0: disable)

The motor will have current wave motion in some specific area. It can improve this situation by

setting this parameter. (When it is high frequency or run with PG, Pr.05-29 can be set to 0.

when the current wave motion happens in the low frequency, please increase Pr.05-29.)

05-31

Accumulative Motor Operation Time (Min.)

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory setting: 00

Settings 00

to1439

05-32

Accumulative Motor Operation Time (Day)

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory setting: 00

Settings

00 to 65535

Pr. 05-31 and Pr.05-32 are used to record the motor operation time. They can be cleared by

setting to 00 and time won’t be recorded when it is less than 60 seconds.