beautypg.com

Group 9 communication parameters – Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 86

background image

Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-37

Group 9 Communication Parameters

Pr.

Explanation

Settings

Factory

Setting

VF VFPG SVC FOCPG TQRPG

09-21

Multi-function Output
Status

0~65535 Read-

only

09-22

AFM2 Status

0~4095

Read-

only

09-23

AFM3 Status

0~4095

Read-

only

Group 10 Speed Feedback Control Parameters
New parameters 10-29~10-30

Pr.

Explanation

Settings

Factory

Setting

VF VFPG SVC FOCPG TQRPG

10-04

ASR (Auto Speed
Regulation) Control ( P) 1

0~40 10

10-06

ASR (Auto Speed
Regulation) Control ( P) 2

0~40 10

10-21 P Gain of Zero Speed

0~40 10

10-29

PG Mechanical Gear A2 1~5000

100

10-30

PG Mechanical Gear B2 1~5000

100

Group 11 Advanced Parameters
Updated parameters 11-00 and 11-09~11-10 and new parameters 11-18~11-40.

Pr.

Explanation

Settings

Factory

Setting

VF

VFPG SVC FOCPG TQRPG

11-00 System Control

bit 0: ASR Auto tuning
bit 1: Inertia estimate
bit 2: Zero Servo
bit 3: Reserved
bit 4: Enable gain adjustment of position loop KP

0

11-07

Detection Time for
Phase-loss

0.01~600.00 sec

0.20

11-08

Reserved

11-09 Level of Phase-loss

0.0~320.0 60.0

11-10

Speed Feed Forward
Gain

0~100% 0

11-11

Zero-speed
Bandwidth

0~40Hz 10

11-12

Speed Response of
Flux Weakening Area

0: Disable
0~150%

65

11-13 Notch Filter Depth

0~20db 0

11-14

Notch Filter
Frequency

0.00~200.00 0.00

11-15

Gain Value of Slip
Compensation

0.00~1.00 1.00

11-16

Low-pass Filter Time
of Keypad Display

0.001~65.535sec 0.100

11-17

Low-pass Filter Time
of PG2 Pulse Input

0.000~65.535sec 0.100

11-18 APR Gain

0.00~40.00 10.00

11-19 APR Curve Time

0.00~655.35 sec

3.00

11-20

|

11-28

Reserved

11-29

Accumulative
Operation Time of
Phase-loss

0~65535 (hour)

0

11-30

|

11-40

Reserved