Srad rpm / 2 60 – Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 166

Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04
4-117
07-28
Torque Offset Setting
Unit: 0.1
Control
mode
SVC
FOCPG
TQRPG
Factory Setting: 0.0
Settings 0.0
to
100.0%
This parameter is torque offset. The motor rated torque is 100%.
07-29
High Torque Offset
Unit: 0.1
Control
mode
SVC
FOCPG
TQRPG
Factory Setting: 30.0
Settings
0.0
to
100.0%
07-30
Middle Torque Offset
Unit: 0.1
Control
mode
SVC
FOCPG
TQRPG
Factory Setting: 20.0
Settings
0.0
to
100.0%
07-31
Low Torque Offset
Unit: 0.1
Control
mode
SVC
FOCPG
TQRPG
Factory Setting: 10.0
Settings
0.0
to
100.0%
When it is set to 3, the source of torque offset will decide to Pr.07-29, Pr.07-30 and Pr.07-31
by the multi-function input terminals setting (31, 32 or 33). The motor rated torque is 100%.
07-32
Forward Motor Torque Limit
Unit: 1
07-33
Forward Regenerative Torque Limit
Unit: 1
07-34
Reverse Motor Torque Limit
Unit: 1
07-35
Reverse Regenerative Torque Limit
Unit: 1
Control
mode
FOCPG
TQRPG
Factory Setting: 200
Settings
0 to 500%
The motor rated torque is 100%. The settings for Pr.07-32 to Pr.07-35 will compare with Pr.03-
00=7, 8, 9, 10. The minimum of the comparison result will be torque limit as shown in the
following figure.
According to the formula of motor rated torque:
)
/
(
)
(
)
.
(
s
rad
W
P
M
N
T
ω
=
, where P(ω) is Pr.05-
02 and W(rad/s) is Pr.05-03.
s
rad
RPM
/
2
60
=
×
π