Chapter 4 Parameters|

4-44

Revision August 2008, 03VE, SW V2.04


00-09

Energy Saving Gain

Unit: 1

Control

mode

FOCPG

Factory setting: 100%

Settings

10~1000

%

When Pr.00-19 is set to1, this parameter can be used for energy saving. The setting should be

decreased when the energy saving is not well. When the motor is vibrated, the setting should

be increased.

00-10

Control Method

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory setting: 0

Settings

0

V/f

control

1

V/f + Encoder (VFPG)

2

Sensorless vector control (SVC)

3

FOC vector control + Encoder (FOCPG)

4

Torque control + Encoder (TQRPG)

This parameter determines the control method of the AC motor drive:

Setting 0: user can design V/f ratio by requirement and control multiple motors simultaneously.

Setting 1: User can use PG card with Encoder to do close-loop speed control.

Setting 2: To have optimal control characteristic by auto-tuning.

Setting 3: To increase torque and control speed precisely. (1:1000)

Setting 4: To increase accuracy for torque control.

00-11

V/f Curve Selection

Control

mode

VF

VFPG

Factory setting: 0

Settings

0

V/f curve determined by group 01

1

1.5

power

curve

2

Square

curve

When it is set to 0, the V/f curve setting for the motor 1 is according to Pr.01-01~Pr.01-08 and

Pr. 01-35~01-42 are for the motor 2.

When setting to 1 or 2, the settings of the 2

nd

voltage/frequency and the 3

rd

voltage/frequency

are invalid.