Chapter 6 Fault Code Information and Maintenance|

6-2

Revision August 2008, 03VE, SW V2.04

Fault Name

Fault Descriptions

Corrective Actions

Ground fault

When (one of) the output terminal(s) is
grounded, short circuit current is more than
50% of AC motor drive rated current, the AC
motor drive power module may be damaged.
NOTE: The short circuit protection is
provided for AC motor drive protection,
not for protection of the user.

1. Check the wiring connections between the

AC motor drive and motor for possible
short circuits, also to ground.

2. Check whether the IGBT power module is

damaged.

3. Check for possible poor insulation at the

output line.

Short-circuit is
detected between
upper bridge and
lower bridge of the
IGBT module

Return to the factory

DC BUS over-voltage
during acceleration
(230V: DC 450V;
460V: DC 900V)

DC BUS over-voltage
during deceleration
(230V: DC 450V;
460V: DC 900V)

DC BUS over-voltage
in constant speed
(230V: DC 450V;
460V: DC 900V)

1.

Check if the input voltage falls within the
rated AC motor drive input voltage range.

2. Check

for

possible voltage transients.

3.

If DC BUS over-voltage due to
regenerative voltage, please increase the
Deceleration Time or add an optional
brake resistor.

Hardware failure in
voltage detection

Check if input voltage is within specification
range and monitor if there is surge voltage.

DC BUS voltage is
less than Pr.06-00
during acceleration

DC BUS voltage is
less than Pr.06-00
during deceleration

DC BUS voltage is
less than Pr.06-00 in
constant speed

DC BUS voltage is
less than Pr.06-00 at
stop

1.

Check if the input voltage is normal

2. Check

for

possible sudden load

Phase Loss

Check Power Source Input if all 3 input phases
are connected without loose contacts.
For models 40hp and above, please check if
the fuse for the AC input circuit is blown.