Chapter 4 Parameters|
4-46
Revision August 2008, 03VE, SW V2.04
When Pr.00-13 is set to 0.
1
2
01-00
01-12
01-14
01-16
01-18
01-13
01-15
01-17
01-19
01-05
1
2
Frequency
Max.
Frequency
Min.
Frequency
accel. time
Time
decel. time
Accel./Decel. Time
When Pr.00-13 is set to 3.
00-14
Time Unit for Acceleration/Deceleration and S Curve
Control
mode
VF VFPG SVC
FOCPG
Factory setting: 0
Settings
0
Unit:
0.01
second
1
Unit:
0.1
second
This parameter determines the time unit for the Acceleration/Deceleration setting. Refer to
Pr.01-12 ~ Pr.01-19 (accel./decel. Time 1 to 4), Pr. 01-20~Pr.01-21 (JOG accel./decel. Time)
and Pr. 01-24~Pr.01-27 (S curve accel./decel. Time).
00-15
Reserved
00-16
Reserved
00-17
Carrier Frequency
Unit: 1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory setting: 10
Settings
1~15kHz
This parameter determinates the PWM carrier frequency of the AC motor drive.
230V/460V Series
Models
1-5HP
0.75-3.7kW
7.5-25HP
5.5-18.5kW
30-60HP
22-45kW
75-100HP
55-75Kw
Setting Range
01~15kHz 01~15kHz 01~09kHz
01~06kHz
Factory Setting
10kHz
9kHz 6kHz 6kHz
1kHz
8kHz
15kHz
Carrier
Frequency
Acoustic
Noise
Electromagnetic
Noise or Leakage
Current
Heat
Dissipation
Current
Wave
Significant
Minimal
Minimal
Minimal
Significant
Significant