Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-93

05-24

Torque Compensation Gain

Unit: 1

Control

mode

VF

VFPG

Factory setting: 0

Settings 0

to10

This parameter may be set so that the AC motor drive will increase its voltage output to obtain

a higher torque. Only to be used for SVC control mode.

Too high torque compensation can overheat the motor.

05-25

Slip Compensation Gain

Unit: 0.01

Control

mode

VF

SVC

Factory setting: 0.00

Settings 0.00

to10.00

When the asynchronous motor is driven by the drive, the load and slip will be increased. This

parameter can be used to correct frequency and lower the slip to make the motor can run near

the synchronous speed under rated current. When the output current is larger than the motor

no-load current, the drive will compensate the frequency by Pr.05-25 setting. If the actual

speed is slower than expectation, please increase the setting and vice versa.

It is only valid in SVC/VF mode.

The factory settings are:

A. In SVC mode, the factory setting is 1.00.

B. In VF mode, the factory setting is 0.00.

05-26

Slip Deviation Level

Unit: 1

Control

mode

VFPG

SVC

FOCPG

Factory setting: 0

Settings

0 to 1000% (0: disable)

05-27

Detection time of Slip Deviation

Unit: 0.1

Control

mode

VFPG

SVC

FOCPG

Factory setting: 1.0

Settings

0.0 to 10.0 sec

05-28

Over Slip Treatment

Control

mode

VFPG

SVC

FOCPG

Factory setting: 0

Settings

0

Warn and keep operation

1

Warn and ramp to stop

2

Warn and coast to stop