Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-57

01-27

S-curve for Deceleration Arrival Time 2

Unit: 0.1/0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.2/0.0

Settings

0.00~25.00 sec /0.00~250.0 sec

It is used to give the smoothest transition between speed changes. The accel./decel. curve

can adjust the S-curve of the accel./decel. When it is enabled, the drive will have different

accel./decel. curve by the accel./decel. time.

The S-curve function is disabled when Pr.00-13 is set to 0.

The Actual Accel. Time = selected accel. Time + (Pr.01-24 + Pr.01-25)/2

The Actual Decel. Time = selected decel. Time + (Pr.01-26 + Pr.01-27)/2

01-24

01-25

01-26

01-27

Frequency

Time

01-28

Skip Frequency 1 (upper limit)

Unit: 0.01

01-29

Skip Frequency 1 (lower limit)

Unit: 0.01

01-30

Skip Frequency 2 (upper limit)

Unit: 0.01

01-31

Skip Frequency 2 (lower limit)

Unit: 0.01

01-32

Skip Frequency 3 (upper limit)

Unit: 0.01

01-33

Skip Frequency 3 (lower limit)

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.00

Settings

0.00~600.00Hz

These parameters are used to set the skip frequency of the AC drive. The skip frequencies are

useful when a motor has vibration at a specific frequency bandwidth. By skipping this

frequency, the vibration will be avoided.



01-34

Mode Selection when Frequency< Fmin

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0

Settings

0

Output

Waiting

1

Zero-speed operation