Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 146

Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04
4-97
Over-Current
Detection Level
06-04
Output Current
Output
Frequency
Over-Current Stall
Prevention during
Operation, output
frequency decrease
over-current stall prevention during operation
Time
06-05
Accel./Decel. Time Selection of Stall Prevention at Constant Speed
Control
mode
VF
VFPG
SVC
Factory Setting: 0
Settings
0
by current accel/decel. time
1
by the 1
st
accel/decel. time
2
by the 2
nd
accel/decel. time
3
by the 3
rd
accel/decel. time
4
by the 4
th
accel/decel. time
5
by auto accel/decel. time
It is used to set the accel./decel. Time selection when stall prevention occurs at constant
speed.
06-06
Over-torque Detection Selection (OT1)
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0
Settings
0
Over-Torque detection disabled.
1
Over-torque detection during constant speed operation, continue to
operate after detection
2
Over-torque detection during constant speed operation, stop
operation after detection
3
Over-torque detection during operation, continue to operate after
detection
4
Over-torque detection during operation, stop operation after
detection
06-07
Over-torque Detection Level (OT1)
Unit: 1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 150