Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-97

Over-Current
Detection Level

06-04

Output Current

Output

Frequency

Over-Current Stall

Prevention during
Operation, output

frequency decrease

over-current stall prevention during operation

Time

06-05

Accel./Decel. Time Selection of Stall Prevention at Constant Speed

Control

mode

VF

VFPG

SVC

Factory Setting: 0

Settings

0

by current accel/decel. time

1

by the 1

st

accel/decel. time

2

by the 2

nd

accel/decel. time

3

by the 3

rd

accel/decel. time

4

by the 4

th

accel/decel. time

5

by auto accel/decel. time

It is used to set the accel./decel. Time selection when stall prevention occurs at constant

speed.

06-06

Over-torque Detection Selection (OT1)

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Over-Torque detection disabled.

1

Over-torque detection during constant speed operation, continue to
operate after detection

2

Over-torque detection during constant speed operation, stop
operation after detection

3

Over-torque detection during operation, continue to operate after
detection

4

Over-torque detection during operation, stop operation after
detection



06-07

Over-torque Detection Level (OT1)

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 150