Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 130

background image

Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-81

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory setting: 0

Settings

0

Zero

bias

1

Lower than bias=bias

2

Greater

than

bias=bias

3

The absolute value of the bias voltage while serving as the center

4

Serve bias as the center

In a noisy environment, it is advantageous to use negative bias to provide a noise margin. It is

recommended NOT to use less than 1V to set the operation frequency.

1 0V

5

1 2 3 4

-1

-2

-3

-4

-5

-1 0V

6 7 8 9

03-00

to

03-02

-6

-7

-8

-9

0

1

2

3

4

4

2

2

4

2

03-09~03-11 gain is positive

4

Z er o bias

Lower than bias =bias

Gr eater than bias= bi as

T he absolute value of the bias voltage
while s erving as the c enter

Serv e bias as the center

bias

bias

Positiv e bias

Negativ e bias

03-09

Analog Input Gain 1 (AVI)

Unit: 1

03-10

Analog Input Gain 1 (ACI)

Unit: 1

03-11

Analog Input Gain 1 (AUI)

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory setting: 100.0

Settings -500.0~500.0%

Parameters 03-03 to 03-11 are used when the source of frequency command is the analog

voltage/current signal.

03-12

ACI/AVI2 Selection

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory setting: 0

Settings

0

ACI

1

AVI

2

There are two AVI analog inputs can be used when this parameter is set to 1 and the SW2 on

the control board is set to AVI2. At this moment, ACI is for voltage input.

03-13

Analog Input Delay Time (AVI)

Unit: 0.01