Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 130

Chapter 4 Parameters|
Revision August 2008, 03VE, SW V2.04
4-81
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory setting: 0
Settings
0
Zero
bias
1
Lower than bias=bias
2
Greater
than
bias=bias
3
The absolute value of the bias voltage while serving as the center
4
Serve bias as the center
In a noisy environment, it is advantageous to use negative bias to provide a noise margin. It is
recommended NOT to use less than 1V to set the operation frequency.
1 0V
5
1 2 3 4
-1
-2
-3
-4
-5
-1 0V
6 7 8 9
03-00
to
03-02
-6
-7
-8
-9
0
1
2
3
4
4
2
2
4
2
03-09~03-11 gain is positive
4
Z er o bias
Lower than bias =bias
Gr eater than bias= bi as
T he absolute value of the bias voltage
while s erving as the c enter
Serv e bias as the center
bias
bias
Positiv e bias
Negativ e bias
03-09
Analog Input Gain 1 (AVI)
Unit: 1
03-10
Analog Input Gain 1 (ACI)
Unit: 1
03-11
Analog Input Gain 1 (AUI)
Unit: 1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory setting: 100.0
Settings -500.0~500.0%
Parameters 03-03 to 03-11 are used when the source of frequency command is the analog
voltage/current signal.
03-12
ACI/AVI2 Selection
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory setting: 0
Settings
0
ACI
1
AVI
2
There are two AVI analog inputs can be used when this parameter is set to 1 and the SW2 on
the control board is set to AVI2. At this moment, ACI is for voltage input.
03-13
Analog Input Delay Time (AVI)
Unit: 0.01