Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-161

After finishing estimating and set Pr.11-00=1 (auto tuning), using Pr.11-04 to reduce overshoot.

Please adjust PDFF gain value by actual situation.

Besides traditional PI control, it also provides PDFF function to reduce overshoot for speed

control.

1. Get Pr.11-01 value

2. Set Pr.11-00 to 1

3. Adjust Pr.11-04 (the larger number is set and the suppressed overshoot function will be

better. But it needs to be used by the actual condition)

PI

PDFF

It is recommended to disable

this function (Pr.11-04=0) for
Y/ connection switch and

ASR1/ASR2 switch application.

11-05

Gain Value of Flux Weakening Curve for Motor 1

Unit: 1

Control

mode

FOCPG

Factory Setting: 90

Settings

0 to 200%

It is used to adjust the output voltage of flux weakening curve.

For the spindle application, the adjustment method is

1. It is used to adjust the output voltage when exceeding rated frequency.

2. Monitor the output voltage

3. Adjust Pr.11-05 (motor 1) or Pr.11-06 (motor 2) setting to make the output voltage reach

motor rated voltage.

4. The larger number it is set, the larger output voltage you will get.