Chapter 4 Parameters|

4-126

Revision August 2008, 03VE, SW V2.04

08-22

Wind Mode

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Rewind

1

Unwind

08-23

Mechanical Gear Ratio A

Unit: 1

08-24

Mechanical Gear Ratio B

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 100

Settings

1 to 65535

1:10

10:1

Application without Encoder

Driv er

Motor

mechanical
gear ratio A

Load

Gear ratio

mechanical
gear ratio B

08-25

Source of the Tension Command/Line Speed

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Parameter

setting

(Pr.08-26)

1

RS-485 communication setting (Pr.08-26)

2

Analog input (Pr. 03-00~03-02 is set to 14 PID target value of
tension, 03-00~03-02 is set to 12 line speed)

08-26

PID Target Value of Tension/Line Speed

Unit: 0.1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 50.0

Settings 0.0

to

100.0%

The setting range is from 0.0 to 100.0%. In tension mode, when Pr.08-21 is set to 1 (Closed-

loop, speed mode), the corresponding value for 100% of dancer is 10V.

In tension mode, when Pr.08-21 is set to 2 (Line speed, speed mode), the corresponding value

for 100% of line speed is max. line speed (Pr.08-38).


08-27

Source of Tension/Line Speed PID Feedback