Correct wiring

DC

power

reactor

reactor

AC motor drive

motor

silicon rectifier


Application 3

Question

Used to improve the input power factor, to

reduce harmonics and provide protection
from AC line disturbances. (surges, switching
spikes, short interruptions, etc.). AC line
reactor should be installed when the power
supply capacity is 500kVA or more and
exceeds 6 times the inverter capacity, or the
mains wiring distance

10m.

When power capacity is too large, line

impedance will be small and the charge
current will be too large. That may damage
AC motor drive due to higher rectifier
temperature.


Correct wiring

large-capacity
power

reactor

small-capacity
AC motor drive

motor