Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 83

Chapter 4 Parameters|
4-34
Revision August 2008, 03VE, SW V2.04
Pr.
Explanation
Settings
Factory
Setting
VF VFPG SVC FOCPG TQRPG
39: Ground current detection error (Hd3)
○
○
○
○
○
40: Auto tuning error (AuE)
○
○
○
41: PID feedback loss (AFE)
○
○
○
○
○
42: PG feedback error (PGF1)
○
○
○
43: PG feedback loss (PGF2)
○
○
○
44: PG feedback stall (PGF3)
○
○
45: PG slip error (PGF4)
○
○
46: PG ref input error (PGr1)
○
○
○
○
○
47: PG ref loss (PGr2)
○
○
○
○
○
48: Analog current input loss (ACE)
○
○
○
○
○
49: External fault input (EF)
○
○
○
○
○
50: Emergency stop (EF1)
○
○
○
○
○
51: External Base Block (B.B.)
○
○
○
○
○
52: Password error (PcodE)
○
○
○
○
○
53:
Reserved
○
○
○
○
○
54: Communication error (cE1)
○
○
○
○
○
55: Communication error (cE2)
○
○
○
○
○
56: Communication error (cE3)
○
○
○
○
○
57: Communication error (cE4)
○
○
○
○
○
58: Communication Time-out (cE10)
○
○
○
○
○
59: PU time-out (cP10)
○
○
○
○
○
60: Brake transistor error (bF)
○
○
○
○
○
61: Y-connection/
Δ-connection switch error (ydc)
○
○
○
○
62: Decel. Energy Backup Error (dEb)
○
○
○
○
○
63: Slip error (oSL)
○
○
○
○
64: Broken belt error (bEb)
○
○
○
○
○
65: Error PID feedback signal of tension (tdEv)
○
○
○
○
○
06-32
Output Frequency for
Malfunction
0.00~655.35 Hz
0.00
○
○
○
○
○
06-33
Output AC Voltage for
Malfunction
0.0~6553.5 V
0.0
○
○
○
○
○
06-34
DC Voltage for
Malfunction
0.0~6553.5 V
0.0
○
○
○
○
○
06-35
Current Value for
Malfunction
0.00~655.35 Amp
0.00
○
○
○
○
○
06-36
IGBT Temperature for
Malfunction
0.0~6553.5 °C
0.0
○
○
○
○
○
Group 8 High-function PID Parameters
New parameters 08-21~08-99
Pr.
Explanation
Settings
Factory
Setting
VF VFPG SVC FOCPG TQRPG
08-00
Input Terminal for PID
Feedback
0: No function
1: Negative PID feedback from external terminal AVI
(Pr.03-00)
2: Negative PID feedback from PG card (Pr.10-15,
skip direction)
3: Negative PID feedback from PG card (Pr.10-15)
4: Positive PID feedback from external terminal AVI
(Pr.03-00)
5: Positive PID feedback from PG card (Pr.10-15,
skip direction)
6: Positive PID feedback from PG card (Pr.10-15)
0
○
○
○
○
08-01
Proportional Gain (P)
0.0~500.0%
80.0
○
○
○
○
0: Disable
0
○
○
○
○
08-21
Tension Control
Selection
1: Closed-loop, speed mode
○
○
○
○
2: Line speed, speed mode
○
○
○
○
3: Reserved
4: Open-loop, torque mode
○