Chapter 4 Parameters|

4-112

Revision August 2008, 03VE, SW V2.04

In PG control mode, the AC motor drive will execute the speed search function automatically

by the PG speed when this setting isn’t set to 0.

07-13

Decel. Time Selection for Momentary Power Loss (DEB function)

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Disable

1

1st

decel.

time

2

2nd

decel.

time

3

3rd

decel.

time

4

4th

decel.

time

5

Current decel. time

6

Auto decel. time

This parameter is used for the decel. time selection for momentary power loss.

07-14

DEB Return Time

Unit: 0.1

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.0

Settings

0.0 to 25.0 sec

The DEB (Deceleration Energy Backup) function is the AC motor drive decelerates to stop

after momentary power loss. When the momentary power loss occurs, this function can be

used for the motor to decelerate to 0 speed with deceleration stop method. When the power is

on again, motor will run again after DEB return time.

Status 1: Insufficient power supply due to momentary power-loss/unstable power (due to low

voltage)/sudden heavy-load