Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 163

Chapter 4 Parameters|
4-114
Revision August 2008, 03VE, SW V2.04
07-15
Dwell Time at Accel.
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0.00
Settings
0.00 to 600.00 sec
07-16
Dwell Frequency at Accel.
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0.00
Settings
0.00 to 600.00 Hz
07-17
Dwell Time at Decel.
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0.00
Settings
0.00 to 600.00 sec
07-18
Dwell Frequency at Decel.
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG
Factory Setting: 0.00
Settings
0.00 to 600.00 Hz
In the heavy load situation, Dwell can make stable output frequency temporarily.
Pr.07-15 to Pr.07-18 is for heavy load to prevent OV or OC occurs.
Frequency
Time
Dwell at accel./decel.
07-16
Dwell
Frequency
at Accel.
07-15
Dwell Time
at Accel.
07-17
Dwell Time
at Decel.
07-18
Dwell
Frequency
at Decel.
07-19
Fan Control
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0
Settings
0
Fan always ON
1
1 minute after AC motor drive stops, fan will be OFF
2
AC motor drive runs and fan ON, AC motor drive stops and fan OFF
3
Fan ON to run when preliminary heat sink temperature attained
4
Fan always OFF
This parameter is used for the fan control.