Chapter 4 Parameters|

4-114

Revision August 2008, 03VE, SW V2.04

07-15

Dwell Time at Accel.

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.00

Settings

0.00 to 600.00 sec

07-16

Dwell Frequency at Accel.

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.00

Settings

0.00 to 600.00 Hz

07-17

Dwell Time at Decel.

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.00

Settings

0.00 to 600.00 sec

07-18

Dwell Frequency at Decel.

Unit: 0.01

Control

mode

VF VFPG SVC

FOCPG

Factory Setting: 0.00

Settings

0.00 to 600.00 Hz

In the heavy load situation, Dwell can make stable output frequency temporarily.

Pr.07-15 to Pr.07-18 is for heavy load to prevent OV or OC occurs.

Frequency

Time

Dwell at accel./decel.

07-16
Dwell
Frequency

at Accel.

07-15

Dwell Time

at Accel.

07-17

Dwell Time

at Decel.

07-18

Dwell

Frequency
at Decel.

07-19

Fan Control

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0

Fan always ON

1

1 minute after AC motor drive stops, fan will be OFF

2

AC motor drive runs and fan ON, AC motor drive stops and fan OFF

3

Fan ON to run when preliminary heat sink temperature attained

4

Fan always OFF

This parameter is used for the fan control.